产品概述


Standard Input Protection
•Standard Interrupt Circuit Breaker
•Under/Over Voltage
•Mechanical Door Interlock
•Loss of Phase
•Surge Protection, C62.41, B

Standard Output Protection
•Contactor
•Under/Overvoltage
•Output Overload/Overcurrent
•Overtemperature

Output Options
•Standard Interrupt Circuit Breaker

Mechanical
•Input / Output Gland Plates
•Mounting Feet with Anchor Holes
•Indoor (Nema 12)

Maintenance Access
•Front Access Only for all repairs
•No Back Access for repair
•No Side Access for repair

 Built in Diagnostics
•Input Undervoltage
•Input Overvoltage
•Output Overcurrent
•Output Overvoltage
•Output Undervoltage
•Over Temperature

Standard Controls
•Start  Pushbutton
•Stop Pushbutton
•Reset Pushbutton
•Emergency Stop Button
•Contactor Open
•Contactor Close

Standard Display
•Input Current, 3 phase
•Input Voltage, 3 phase
•Input KW
•Output Current, 3 phase
•Output Voltage, 3 phase
•Ouptut KW
•Elapsed Time Meter

Standard Annunciation Lamps
•Input Available
•Inverter Power
•Output Contactor
•System Alarm
•Output Overload
•Audible Alarm Disabled

Standard Annunciation LED's
•Input Undervoltage
•Input Overvoltage
•Output Overcurrent
•Output Overvoltage
•Output Undervoltage
•Over Temperature

400 Hz Application
•E & F Selector Switch
•E & F Front Panel Bypass Light
•Aircraft Interlock Bypass Switch
•0-7% Auto Voltage Compensation
•Remote Sensing Control

Ventilation
•Front Ventilation- Intake Only
•Left/Right Side- Ventilation OK
•Bottom - Ventilation OK
•Top - Ventilation OK with approval
•No Rear Ventilation

Other Internal Performance Specifications

1、  Upon Power Up sequence, unit should not "alarm" during power up
2、  Internal Thermal LimitsDuring 100% Resistive Load Test, after temperature obtains equilibrium (stabilization):   4-6 hours small units, 8-10 hours large units)
      A )Limit of 10ºC Temperature Rise in Cabinet from input Ambient Air to Output Air
      B) Maximum IGBT Junction Temperature should be limited to 107º - 115ºC
      C )Maximum Heatsink Temperature should be  < 85ºC
      D )Temperature Extended from Ambient to +55ºC can be done with calculation of (55ºC - ambient) x 1.3 as a rule of thumb to add values
3、  Fans should be properly rated at 65ºC minimum
4、  Transformers & Magnetics4Transformers, chokes should be Class H Insulation and operate at no more than 110-120ºC
5、  All transformers & wire to be copper
6、  DC Capacitors No greater than 75% utilization of DC buss to Capacitor Rating (example:  540V/900VDC = 60%)
7、  All capacitors should be 85ºC rated or higher
8、  < 1% RMS Ripple on DC Buss (example: 4 Volts RMS / 540 VDC Buss = 0.7% ripple)
9、  Thermal Design SoftwareIt is highly recommended that:aThermal Simulation software tools be used for overall cabinet thermal design, and bThermal Simulation software tool similar to R-tools.com be used for Heatsink design.
10、 Board & Component MarkingAll Board and component Marking should be removed
11、 Factory TestingFactory Test procedures will be provided by Precision Power, and will be submitted and approved prior to shipment.